Documenting routine visual inspections and annual functional certifications in a standardized checklist maintains building life-safety compliance and ensures audit readiness.

Facility Inspection Checklist Sections

Inspection Category Required Verification Points Pass / Fail Criteria
FACP Control Unit AC power LED lit; zero unaddressed yellow trouble or supervisory LEDs; display time accurate Normal standby state with 0 active faults
Standby Batteries Check terminal torque; measure float voltage (27.2V - 27.6V on 24V system); conduct 30-minute load test Holds minimum voltage under load; replaced if > 4 years old
Initiating Devices Aerosol test smoke detectors; activate manual pull stations; test duct detector air pressure 100% devices report correct address and description to FACP
Notification Circuits Verify all horn/strobe NAC circuits fire; check strobe flash synchronization; measure dBA audibility Sound pressure meets 15 dBA above ambient; strobes flash in sync
Central Station Dispatch Confirm alarm, supervisory, and trouble signals received at monitoring center with correct zone codes Transmission confirmed by monitoring operator