Commercial fire alarm systems protect large multi-tenant buildings, industrial plants, and healthcare facilities. Statutory Inspection, Testing, and Maintenance (ITM) ensures system reliability and regulatory compliance.

NFPA 72 Commercial ITM Schedule

Component Visual Inspection Functional Test Testing Standard & Procedure
FACP Control Unit Weekly / Monthly Annual Verify normal AC power, trouble LED lamps, fuse integrity, and interconnect relays
Secondary Batteries Monthly Semi-Annual Load-voltage test on sealed lead-acid cells; verify 24-hr standby + 5-min alarm capacity
Smoke Detectors Semi-Annual Annual Test using aerosol smoke spray or calibrated dispenser; verify address at FACP
Duct Smoke Detectors Semi-Annual Annual Verify sampling tube differential pressure with digital manometer; test HVAC fan shutdown
Manual Pull Stations Semi-Annual Annual Manual mechanical pull; verify address latch and panel receipt within 10 seconds
Audible & Visual Appliances Semi-Annual Annual Measure sound pressure (dBA) with calibrated sound level meter; verify strobe flash sync